Intrinsic Safety Isolator, Temperature R
937 Isolated Barrier, 12.5mm Module (High Density), Analog In I/O Type, Repeater, Resistance Measuring, 24V DC, Single Channel
1-Channel Isolated Barrier 24V DC Supply (Power Rail) Resistance and RTD input (Pt100,Pt500, Pt1000) Resistance output Accuracy 0.1% Line faulty detection (LFD) for Pt100 Housing Width 12.5mm This isolated barrier is used for intrinsic safety applications. It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas. A 2-, 3-, or 4-wire technique is available depending on the required accuracy. The input card of the control system measures the same load as if it were connected directly to the resistance in a hazardous area